Open main menu
Home
Random
Recent changes
Special pages
Community portal
Preferences
About Wikipedia
Disclaimers
Incubator escapee wiki
Search
User menu
Talk
Dark mode
Contributions
Create account
Log in
Editing
Current loop
(section)
Warning:
You are not logged in. Your IP address will be publicly visible if you make any edits. If you
log in
or
create an account
, your edits will be attributed to your username, along with other benefits.
Anti-spam check. Do
not
fill this in!
==Process control 4β20 mA loops== [[File:Analogue control loop evolution.png|thumb|Showing the evolution of analogue control loop signalling from the pneumatic era to the electronic era]] [[File:Smart current loop positioner.png|thumb|Example of current loops used for sensing and control transmission. Specific example of a smart valve positioner is shown.]] In industrial [[process control]], [[analog signal|analog]] 4β20 mA current loops are commonly used for electronic signalling, with the two values of 4 and 20 mA representing 0β100% of the range of measurement or control. These loops are used both for carrying sensor information from field instrumentation and carrying control signals to the process modulating devices, such as a valve. The key advantages of the current loop are: * The loop can often power the remote device, with power supplied by the controller, thus removing need for power cabling. Many instrumentation manufacturers produce 4β20 mA sensors which are "loop powered". * The "live" or "elevated" zero of 4 mA allows powering of the device even with no process signal output from the field transmitter. * The accuracy of the signal is not affected by voltage drop in the interconnecting wiring. * It has high noise immunity, as it is low-impedance circuit, usually through twisted-pair conductors. * It is self-monitoring; currents less than 3.8 mA or more than 20.5 mA are taken to indicate a fault.<ref>NAMUR standard NE 043 "Standardisation of the Signal Level for the Failure Information of Digital Transmitters".</ref> * It can be carried over long cables up to the limit of the resistance for the voltage used. * Inline displays can be inserted and powered by the loop, as long as total allowable loop resistance is not exceeded. * Easy conversion to voltage using a resistor. * Loop-powered "I to P" (current to pressure) converters can convert the 4β20 mA signal to a 3β15 psi pneumatic output for control valves, allowing easy integration of 4β20 mA signals into existing pneumatic plant. Field instrumentation measurements include [[pressure]], [[temperature]], level, [[Volumetric flow rate|flow]], [[pH]] or other process variables. A current loop can also be used to control a valve positioner or other output [[actuator]]. Since input terminals of instruments may have one side of the current loop input tied to the chassis ground (earth), analog isolators may be required when connecting several instruments in series. The relationship between current value and process variable measurement is set by calibration, which assigns different ranges of engineering units to the span between 4 and 20 mA. The mapping between engineering units and current can be inverted, so that 4 mA represents the maximum and 20 mA the minimum. ===Active and passive devices=== Depending on the source of current for the loop, devices may be classified as ''active'' (supplying or "sourcing" power) or ''passive'' (relying on or "sinking" loop power). For example, a [[chart recorder]] may provide loop power to a pressure transmitter. The pressure transmitter modulates the current on the loop to send the signal to the strip chart recorder, but does not in itself supply power to the loop and so is passive. Another loop may contain two passive chart recorders, a passive pressure transmitter, and a 24 V battery (the battery is the active device). Note that a ''4-wire'' instrument has a power-supply input separate from the current loop. Panel mount displays and chart recorders are commonly termed "indicator devices" or "process monitors". Several passive indicator devices may be connected in series, but a loop must have only one transmitter device and only one power source (active device). ===Evolution of analogue control signals=== [[Image:Pl control valve.jpg|thumb|right|Control valve with pneumatic diaphragm actuator and "smart" 4β20 mA positioner which will also feed back the actual valve position and status over the current loop]] The 4β20 mA convention was born in the 1950s out of the earlier highly successful 3β15 psi pneumatic control signal standard, when electronics became cheap and reliable enough to emulate the older standard electrically. The 3β15 psi standard had the same features of being able to power some remote devices, and have a "live" zero. However, the 4β20 mA standard was better suited to the electronic controllers being developed at the time. The transition was gradual and has extended into the 21st century, due to the huge installed base of 3β15 psi devices. As the operation of pneumatic valves over motorised valves has many cost and reliability advantages, pneumatic actuation is still an industry standard. To allow the construction of hybrid systems, where the 4β20 mA is generated by the controller, but allows the use of pneumatic valves, a range of current to pressure (I to P) converters are available from manufacturers. These are usually local to the control valve and convert 4β20 mA to 3β15 psi (or 0.2β1.0 bar). This signal is then fed to the valve actuator or, more commonly, a pneumatic positioner. The positioner is a dedicated controller which has a mechanical linkage to the actuator movement. This ensures that problems of friction are overcome and the valve control element moves to the desired position. It also allows the use of higher air pressures for valve actuation. With the development of cheap industrial micro-processors, "smart" valve positioners have become available since the mid-1980s and are very popular for new installations. These include an I to P converter, plus valve position and condition monitoring. These latter are fed back over the current loop to the controller, using protocols such as [[Highway Addressable Remote Transducer Protocol|HART]].
Edit summary
(Briefly describe your changes)
By publishing changes, you agree to the
Terms of Use
, and you irrevocably agree to release your contribution under the
CC BY-SA 4.0 License
and the
GFDL
. You agree that a hyperlink or URL is sufficient attribution under the Creative Commons license.
Cancel
Editing help
(opens in new window)